TRIPP LITE 8-OUTLET 'SMART-PRO' LINE-INTERACTIVE UPS (1.35kW/1.5kVA) - RACKMOUNT


Part # : TRS1500RM
Manufacturer SKU : SMART1500RM2U
Brand : Tripplite
Warranty : 1-year Lin Haw warranty + 2-year warranty, 3 year with registration from manufacturer. Note: Registration is required for 3-year warranty.

Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface

Offers network-grade power protection for critical server, network and telecommunications equipment. Line Interactive Uninterruptible Power Supply (UPS) with built-in Auto-Voltage Regulation (AVR) actively corrects brownouts and overvoltages back to usable levels while maintaining a full battery charge in case of power failure. Interactive LCD interface reports UPS operating mode, detailed UPS and site-power data, plus enables a variety of UPS setup and configuration options. Super-fast switchover from line to battery power occurs within milliseconds to maintain operation of connected equipment without interruption or reboot.

95% line-mode efficiency offers reduced heat emissions and operating costs.

Network management interfaces support communications via USB, RS-232 and optional SNMPWEBCARD network interface. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Network communications ports enable detailed monitoring of equipment load levels, self-test data and utility power conditions.

Includes PowerAlert monitoring software and complete cabling.

Switched output load banks enable scheduled and real-time remote reboot and load shedding of select outlets. Emergency Power Off (EPO) interface. LCD display panel easily rotates for viewing in rackmount or tower configurations. Audible alarm with push-button momentary alarm-cancel and silent-mode configuration options. Programmable self-test.

Field-replaceable, hot-swappable battery modules.

Key Features:

  • Tripp Lite SMART1500RM2U line interactive 2U rack/tower UPS with 1500VA / 1.5kVA / 1350W capacity

  • Line interactive UPS with Automatic Voltage Regulation (AVR) corrects brownouts and overvoltages from 83 to 147V

  • NEMA 5-15P input plug; 6 NEMA 5-15R output receptacles, Two independently switchable output load banks

  • Maintains uninterrupted operation of connected networking equipment during blackouts, surges, brownouts and overvoltages

  • High 95% efficiency rating in line-power mode offers reduced power consumption and BTU emissions

  • Internal batteries offer 13 minutes at 50% load (675W) and 4.5 minutes at 100% load (1350W)

  • Hot-swappable, user-replaceable internal batteries can be replaced with no disruption to connected equipment

  • Front panel LCD monitoring screen with MODE and ENTER buttons reports operating mode with 5-bar battery charge graphic, plus 7 selectable screens of detailed UPS and site power information

  • LCD interface also supports a number of advanced user setup and operating preferences

  • Ships with 4 post rackmount installation hardware; Optional 2POSTRMKITWM enables 2 post rackmount/wallmount installation;

  • Optional 2-9USTAND enables tower placement

  • Built-in USB, RS-232 and optional SNMPWEBCARD accessory monitoring options

  • HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X

  • Included PowerAlert UPS monitoring software; Built-in Emergency Power Off (EPO) interface with cable

Package Includes

  • SMART1500RM2U UPS System

  • PowerAlert software with USB, Serial & EPO cabling

  • 4 post rackmount installation kit

  • Instruction manual

Specifications:

OUTPUT
Output Volt Amp Capacity (VA) 1500
Output kVA capacity (kVA) 1.5
Output Watt Capacity (watts) 1350
Output kW capacity 1.35
Output power factor 0.9
Nominal Output Voltage(s) Supported 120V
Frequency compatibility 60 Hz
Output voltage regulation (line mode) -21%, +8%
Output voltage regulation (Battery mode) +/- 5%
Built-in UPS output receptacles 8 5-15R outlet(s)
Built-in controllable switched load banks Two switchable two-outlet 5-15R load banks
Output AC waveform (AC mode) Sine wave
Output AC waveform (battery mode) Pure Sine wave
INPUT
Rated input current (at maximum load) 12A
Nominal Input Voltage(s) Supported 120V AC
UPS input connection type 5-15P
Input circuit breaker 15A
UPS Input cord length (ft.) 10
UPS Input cord length (m) 3
Recommended Electrical Service 15A 120V
BATTERY
Full load runtime (minutes) 4.5 min. (1350w)
Half load runtime (minutes) 13 min. (675w)
DC system voltage (VDC) 36
Battery recharge rate (included batteries) Less than 4.5 hours from 10% to 90%
Replacement battery cartridge (internal UPS battery replacement) RBC93-2U
Battery Access Front panel battery access door
Battery replacement description Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 147
Overvoltage correction Input voltages between 128 and 147 are reduced by 12%
Undervoltage correction Input voltages between 83 and 107 are boosted by 14%
LEDS ALARMS & SWITCHES
Front panel LCD display Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
Alarms Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
Alarm cancel operation Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
Switches 3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
SURGE / NOISE SUPPRESSION
UPS AC suppression joule rating 570
UPS AC suppression response time Instantaneous
EMI / RFI AC noise suppression Yes
PHYSICAL
Installation form factors supported with included accessories 4 post 19 inch rackmount (mounting rail kit included)
Installation form factors supported with optional accessories 2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)
Primary form factor Rackmount
UPS / Power Module dimensions in primary form factor (height x width x depth / inches) 3.5 x 17.5 x 13.45
UPS / Power Module dimensions in primary form factor (height x width x depth / cm) 8.9 x 44.4 x 34.2
Installed whole system total rack space height (rack spaces) 2U
Secondary form factor Tower (requires 2-9USTAND)
UPS / Power Module weight (lbs) 46.5
UPS / Power Module weight (kg) 21.1
UPS Shipping dimensions (height x width x depth / inches) 9 x 24 x 20.2
UPS Shipping dimensions (height x width x depth / cm) 22.9 x 61 x 51.4
Shipping weight (lbs) 57.6
Shipping weight (kg) 26.2
UPS housing material Steel
Cooling method Fan
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC mode BTU / hr. (full load) 267
COMMUNICATIONS
Communications interface USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Network monitoring port description Supports detailed monitoring of UPS and site power conditions
PowerAlert software Included
Communications cable USB and DB9 cabling included
WatchDog compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time 2-4 milliseconds
Low voltage transfer to battery power (setpoint) 83
High voltage transfer to battery power (setpoint) 147
SPECIAL FEATURES
Grounding lug Back panel grounding lug
Cold Start (startup in battery mode during a power failure) Cold-start operation supported
High availability UPS features Hot swappable batteries
Green & high efficiency features Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
CERTIFICATIONS
UPS Certifications Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category B (EMI)
WARRANTY
Product Warranty Period (Worldwide) 2-year warranty, 3 year with registration. Note: registration is required for 3-year warranty.
Connected Equipment Insurance (U.S., Canada & Puerto Rico) $250,000 Ultimate Lifetime Insurance