| UPS Type | Line‑Interactive |
|---|
| Input Phase | Single‑Phase |
|---|
| Rated Input Current (Maximum Load) | 10 A |
|---|
| Nominal Input Voltage | 120 V AC |
|---|
| UPS Input Connection Type | 5‑15P |
|---|
| Input Circuit Breaker | 10 A |
|---|
| Input Cord Length | 3.1 m (10.2 ft) |
|---|
| Recommended Electrical Service | 15 A 120 V |
|---|
| Maximum Input Amps | 10 A |
|---|
| Output Capacity | 500 VA / 300 W |
|---|
| Power Factor | 0.6 |
|---|
| Output Capacity Details | 4.2 A @ 120 V; 120% load: 5 min (line), 5 sec (battery) |
|---|
| Output Voltage | 120 V |
|---|
| Frequency Compatibility | 60 Hz |
|---|
| Frequency Compatibility Details | Output regulated to ±0.05 Hz when input deviates ±5 Hz |
|---|
| Output Voltage Regulation (Line Mode) | −14% / +16% |
|---|
| Output Voltage Regulation (Battery Mode) | ±5% |
|---|
| Output Receptacles | (6) NEMA 5‑15R (5 UPS + 1 surge‑only) |
|---|
| Load Management | 1 switchable single‑outlet load bank |
|---|
| Waveform (AC Mode) | Sine wave |
|---|
| Waveform (Battery Mode) | PWM sine wave |
|---|
| Individually Controllable Load Banks | Yes |
|---|
| Battery Type | VRLA (lead‑acid) |
|---|
| Runtime (Full Load) | 3 min (300 W) |
|---|
| Runtime (Half Load) | 14 min (150 W) |
|---|
| DC System Voltage | 12 V |
|---|
| Recharge Time | <12 hours to 90% |
|---|
| Battery Access | Door access |
|---|
| Battery Replacement | Hot‑swappable, user replaceable |
|---|
| Voltage Regulation Range | 90–139 V (AVR) |
|---|
| Undervoltage Correction | Boosts 90–105 V input by ~14% |
|---|
| Switches | Power + alarm cancel / self‑test |
|---|
| Audible Alarm | Alerts for power failure, overload, low battery |
|---|
| Alarm Cancel | Yes (via switch) |
|---|
| LED Indicators | 5 LEDs (line, battery, overload, AVR, battery status) |
|---|
| EMI / RFI Filtering | Yes |
|---|
| Surge Protection | 567 J |
|---|
| Response Time | Instantaneous |
|---|
| Form Factor | Rackmount / Tower |
|---|
| Rack Height | 1U |
|---|
| Form Factors Supported | 2‑post & 4‑post rackmount; tower |
|---|
| Minimum Rack Depth | 38.10 cm (15.0 in) |
|---|
| Unit Dimensions (H × W × D) | 4.39 × 43.99 × 28.60 cm (1.7 × 17.3 × 11.3 in) |
|---|
| Primary Dimensions (H × W × D) | 44 × 440 × 286 mm (1.7 × 17.3 × 11.3 in) |
|---|
| Unit Weight | 7.17 kg (15.8 lb) |
|---|
| Shipping Dimensions (H × W × D) | 10.67 × 39.88 × 54.10 cm (4.2 × 15.7 × 21.3 in) |
|---|
| Shipping Weight | 9.64 kg (21.3 lb) |
|---|
| Housing Material | Steel |
|---|
| Mounting Details | Includes brackets for rack and tower installation |
|---|
| Operating Temperature | 0–40°C (32–104°F) |
|---|
| Storage Temperature | −15–50°C (5–122°F) |
|---|
| Humidity | 0–95% non‑condensing |
|---|
| Heat Dissipation | 48 BTU/hr |
|---|
| Efficiency | 97% |
|---|
| Operating Elevation | 0–6562 ft (0–2000 m) |
|---|
| Noise Level | 45 dBA |
|---|
| Software | PowerAlert |
|---|
| Communications Interfaces | DB9, USB (HID), SNMP slot, EPO |
|---|
| Network Management | Optional WEBCARDLXE |
|---|
| Transfer Time | 4–6 ms (10 ms max) |
|---|
| Low Voltage Transfer | 90 V |
|---|
| High Voltage Transfer | 139 V |
|---|
| Cold Start | Supported |
|---|
| Key Features | AVR, hot‑swap batteries, remote management, surge protection |
|---|
| Grounding | Rear grounding lug |
|---|
| Applications | High-end desktop, small network, POS, hospitality |
|---|
| Certifications | CSA, ICES, NOM, UL 1778 |
|---|
| Compliance | ENERGY STAR, FCC Class B, RoHS |
|---|
| Warranty | 2‑year (3‑year with registration) |
|---|
| Equipment Insurance | $250,000 lifetime coverage |
|---|